Home > Products > Chiller > Ice Rink Industry
Ice Rink Industry
Ice Rink Industry -30 Degree Water Chiller
  • Ice Rink Industry -30 Degree Water Chiller
  • Ice Rink Industry -30 Degree Water Chiller
  • Ice Rink Industry -30 Degree Water Chiller
  • Ice Rink Industry -30 Degree Water Chiller

Ice Rink Industry -30 Degree Water Chiller

In case you do not find the type or model in the website We can customized according to your request.
Contact Now
  • Features
  • Technical Data
  • Application
  • Certification
  • Part List
  • Reference

Features
1. Compressor: adopt international brand semi closed 5:6 non symmetrical double screw type air cooled special type compressor.
2. Heat exchanger: evaporator use high efficient shell and tube heat exchanger, condenser use high efficiency copper pipe+hydrophilic aluminum fin; with high pressure, high heat transfer efficiency, maintenance free, long service life, etc.;
3. Control system: using SIEMENS control system, advanced PLC control technology, can accept the programming, perfect communication function;
4. The electrical system: SIEMENS, Schneider and other national brands of electrical components, waterproof type control cabinet;
5. Man-machine interface: Chinese and  English man-machine interface, touch type liquid crystal display operation, simple procedures, one key to start, automatic operation;
6. Chiller maintenance: chiller adopts integral design, compact structure, simple, strong corrosion resistance, with waterproof control cabinet, to ensure that the unit can be placed outside the long-term is not easy to fade, corrosion.
7. The choice of environmental protection type R407C or R134a refrigerant.

Water chiller parameters (output temp -30℃)

Model

 UNIT

SLPW-

6.2h

8.2h

10.2h

12.2h

Cooling capacity

Btu

12624.40

15695.20

22178.00

25931.20

RT

1.05

1.31

1.85

2.16

Kw

3.70

4.60

6.50

7.60

×10³Kcal/h

3.20

4.00

5.60

6.50

 Total Power

KW

4.50

4.90

6.80

8.60

Total Current

A

17.00

23.30

28.70

26.70

       Compressor

 Qty

set

2

2

2

2

Input power

KW

3.70

4.10

6.00

7.50

 Operation Current

A

6.60

7.30

10.70

13.40

 

Condenser

Type

High efficiency copper dry type shell-and-tube heat exchanger

  Cooling Water Flow

L/min

33.00

39.00

55.00

67.00

Water Pipe Connection

mm

25

32

32

32

  Evaporator

 Type

 
Horizontal shell-and-tube/Coil type high efficiency copper heat exchanger

  Chilled water Flow

L/min

13.30

16.60

23.20

27.00

Water pipe connection

mm

25

32

32

32

 

  Chilled Water Pump

Type

 High efficiency, low noise

Input Power

Kw

0.55

0.75

0.75

1.10

Head

m

17

25

24

24

Refrigerant

Type

 
R22

    Water tank Indicating Volume

Liter

190.00

210.00

250.00

250.00

Safety protection

 high and low pressure protection, overload protection, over temperature protection, phase sequence protection, etc.

Dimensions (L*W*H)

 Length

mm

1350

1350

1350

1350

Width

mm

850

850

850

850

  High

mm

1200

1200

1200

1200

 Total Weight

KG

260

290

330

380


Model

 UNIT

SLPW-

3.1h

4.1h

5.1h

6.1h

Cooling capacity

Btu

6482.80

7847.60

11259.60

12965.60

RT

0.54

0.65

0.94

1.08

Kw

1.90

2.30

3.30

3.80

×10³Kcal/h

1.60

2.00

2.80

3.30

 Total Power

KW

2.20

2.40

3.60

4.30

Total Current

A

4.70

8.20

12.10

13.40

       Compressor

 Qty

set

1

1

1

1

Input power

kw

1.90

2.10

3.00

3.80

Operation Current

A

3.30

3.60

5.30

6.70

Condenser

Type

High efficiency copper dry type shell-and-tube heat exchanger

  Cooling Water Flow

L/min

16.00

19.00

28.00

33.00

Water Pipe Connection

mm

20

20

20

25

  Evaporator

 Type

  Horizontal shell-and-tube/Coil type high efficiency copper heat exchanger

  Chilled water Flow

L/min

6.60

8.30

11.60

13.70

Water pipe connection

mm

20

20

20

25

Chilled Water Pump

Type

 High efficiency, low noise     

Input Power

Kw

0.37

0.37

0.37

0.55

Head

m

15

20

19

19

Refrigerant

 Type

 
R22

    Water tank Indicating Volume

Liter

80.00

90.00

190.00

190.00

Safety protection

  high and low pressure protection, overload protection, over temperature protection, phase sequence protection, etc.

Dimensions (L*W*H)

 Length

mm

1200

1200

1200

1350

Width

mm

850

850

850

850

  High

mm

1200

1200

1200

1200

 Total Weight

KG

150

180

210

250


Note:
1, the table refrigeration conditions: chilled glycol water inlet temperature -25 ℃, water outlet temperature -30 ℃, the cooling water temperature 30 ℃, water temperature 35 ℃;
2, this series of units used in low temperature conditions, to use 55% of  the glycol for antifreeze coolants;
3, the series unit uses imported from Europe hermetic compressors, superior performance, strong anti-strike capability liquid; 
4, standard power supply: 380V / 3N-50HZ, voltage fluctuation allowed ± 5%, frequency fluctuation ± 2%; 
5, host the actual head of the pump head minus head losses within the host. (1mH2O = 9.8KPa)
6, In addition to the specifications and requirements, we can provide non-standard products according to customer requirements.
Application:
The cooling ice for professional or recreational rinks. The low temperature chiller will keep the icy state.


Country: Bolivia
Chiller type: water cooled
Cooling capacity: 130kW
Cooling medium: R407C
Supply power: 3P-380V-50Hz
Compressor brand: COPELAND
Compressor type: scroll
Water outlet tem.: 7℃

Country: Philippines
Chiller type: air cooled
Cooling capacity: 130kW
Cooling medium: R22
Supply power: 3P-380V-60Hz
Compressor brand: COPELAND
Compressor type: scroll
Water outlet tem.: 7℃

Country: Malaysia
Chiller type: water cooled
Cooling capacity: 175kW
Cooling medium: R22
Supply power: 3P-380V-50Hz
Compressor brand: HANBELL
Compressor type: screw
Water outlet tem.: 7℃

Country: UAE
Chiller type: air cooled
Cooling capacity: 41kW
Cooling medium: R22
Supply power: 3P-380V-50Hz
Compressor brand: COPELAND
Compressor type: scroll
Water outlet tem.: 7℃

 

 


 


 